TABLE OF MINIMUM TECHNICAL DATAZINC 27 KV metaLLIC OXIDE LINE ARRESTORITEMDEscriptION UNITREQUIREDGUARANTEED11 GENERAL DATA1.1Manufacturer INDICATEHEMG1.2Country of Origin INDICATECHINA1.3Model INDICATEYH10W-271.4Type OZNZNO Lightning arrester1.5Standard IEC 60099-4IEC 60099-41.6Mounting OUTDOOROUTDOOR1.7Class 2 221.8Installation altitude m.s.n.m. MOSLMAJOR THAN 400040001.9Type of conductor of the line OUTDOOROUTDOOR1.10.Line conductor section (*) MM225 TO 12025 TO 1202NOMINAL DATA AND CHARACTERISTICS2.1Rated frequency (fr) HZ60602.2System voltage kV KV22.922.92.3Rated voltage (Ur) KV27272.4Continuous operating voltage (MCOV) KV22222.5Temporary overvoltage at 1 s.KV30302.6Rated discharge current KA10102.7Energy dissipation capacity (double pulse) kJ / kVKJ/KV4.5@UR MIMIMUM4.752.8Maximum residual voltage to the maneuver type impulse at 500 A KV57572.9Maximum residual voltage to the atmospheric discharge impulse to: 5kA KV6767 10kA KV7272 20kA KV80802.10.Body Isolator Silicone Rubber SILICON RUBBERSILICON RUBBER2.11The BIL of the equipment to be protected KV1701702.12Permissible static and dynamic load According to IEC 60099-4 Second Edition (2004-5) NmINDICATE5002.13LEAKAGE DISTANCEMM 100010002.14metal parts protected against corrosion by hot dip galvanizing YESYES2.15Type test (delivery of similar lightning conductor certificate YESYES2.16Integrated Disconnector with Impeller Cartridge according to IEC YESYES2.17Connection terminal to conductor type staple suspension for live line work with installation with shotgun type YESYES2.18Grounding accessories that should include: 25 mm2 copper wire, shackles and connectors suitable for grounding. YESYES3COMPLEMENTARY INFORMATION3.1Dimensional plane equipment YESYES3.2Drawing of the rating plate YESYES3.3Complete connection and metering plan from the clamp to the ground connection. YESYES (*) You should consider 30 staples from 70 to 120 mm2 and the rest from 35 to 70 mm2 YES